Foul water and surface water package pump stations
We supply and install packaged foul and surface water pumping stations, above or below ground, from small domestic chambers to larger stations on housing and commercial developments. Rainwater harvesting chambers and booster sets can be included where the scheme needs them.
Typical packaged GRP stations are offered with chamber diameters from 0.8 to 2.9 metres and vertical depths from 1 to 6.5 metres. Horizontal chambers can be made to the length the site needs. Pump arrangements are single or twin, running as duty only, duty/assist or duty/standby.
- Control panels built to order in the UK, in IP55 mild steel enclosures, with pear-type float controls or ultrasonics.
- A high-level alarm, with volt-free contacts for remote signalling, is standard on all systems.
- Access covers from pedestrian rating up to D400, to suit the location.
- Pumps from established municipal manufacturers, in 230 V or 400 V, with galvanised or ductile iron pipework and sewage-rated valves.
- Bespoke tanks can be delivered to site within 72 hours. A Fast-Trak fit-out is available within 48 hours if required; additional charges may apply.
Stations are designed in accordance with the relevant standards, including BS EN 12050-1 for pumping installations in buildings and sites, BS EN 12056-4 for drainage inside buildings, BS EN 752-6 for drain and sewer pumping stations outside buildings, and Approved Document H1 on foul drainage.